Winter Electrical Checklist for North Hills Homes
Pittsburgh's first freeze in this forecast lands the night of Monday, Nov 16 (low 32°F), with Tuesday night at 30°F. Winter electrical problems are predictable — space heaters on tired circuits, breakers tripping under cold-snap load, heat tape on a tripped GFCI, dead detectors. This is the checklist we work from, in the order that matters.
Text photos of your electrical panel (door open, labels visible) and the outlet or circuit giving you trouble to (412) 326-9761 — that's the fastest way to a real number, and the fastest way for us to tell you if it's a service call or something you can safely check yourself first.
Text photos to (412) 326-9761 Or send photos with the quote formFor jobs over $500, Pennsylvania law (HICPA) requires a signed written contract before any work begins or any payment is taken.
1. Space heaters: the circuit math nobody does
A typical space heater draws about 1,500 watts — roughly 12.5 amps. On a standard 15-amp circuit, that is already over the 80% continuous-load line before anything else in the room is switched on. Add a TV, a lamp, and a phone charger on the same circuit and the breaker is doing exactly what it was built to do.
- Wall outlet only: never an extension cord or power strip — they overheat under a heater's sustained draw.
- One heater per circuit: two heaters on one circuit is a tripped breaker at best.
- Three feet of clearance: from bedding, curtains, furniture, and anything else that can burn. Per NFPA figures cited in current fire-safety guidance, portable space heaters are involved in about two of every five home heating fires, and half of home heating fires happen in December, January, and February.
- Warm outlet, buzzing, or a burning smell = stop: unplug the heater and call. Those are connection failures, not heater quirks.
The full math and the dedicated-circuit fix are in our Space Heater & Winter Electrical Safety Guide.
2. A breaker that trips all winter is telling you something
Cold snaps stack load: heaters, heat tape, a furnace blower running longer, lights on before 5 PM. A breaker that trips once on a genuine overload and then holds is different from one that trips repeatedly on the same circuit under normal use — the second one is a warning about capacity, a failing breaker, or a connection heating up.
- Do not keep resetting it all season and do not swap in a bigger breaker — the wire in the wall is sized to the breaker, not the other way around.
- Note what was running when it tripped and tell us — that pattern is the diagnosis.
- Start here: our Breaker Keeps Tripping guide walks through what each pattern usually means.
3. Before the first freeze: heat tape, sump pump, furnace circuit
With overnight lows of 32°F Monday and 30°F Tuesday in the current Pittsburgh forecast, this week is the check — not after a pipe bursts.
- Heat tape / heat cable: confirm it is plugged into a GFCI-protected outlet and that the GFCI has not tripped. A tripped GFCI is the most common reason pipes freeze even with heat cable installed. Check the GFCI guide for the reset/test steps. Damaged or overlapped cable gets replaced, not taped over.
- Sump pump: pour a bucket of water in the pit and watch it run. Its circuit should not be shared with the space heater warming the basement.
- Furnace: if the blower circuit shares space with new winter loads, that is a panel conversation — see the panel upgrade guide.
4. Detectors: heating season is CO season
Any fuel-burning heat — furnace, fireplace, fuel-burning space heater — makes carbon monoxide protection a winter item, not a spring one.
- Test every smoke and CO alarm this week; replace any alarm past the date printed on it.
- CO alarm on every level and outside sleeping areas.
- Generators stay outdoors, away from windows and doors — the hookup side of that rule is on our generator hookup page.
5. Seasonal load, safely (decorations included)
December load is real even before any decorations go up: earlier darkness, more cooking, more heaters. If you do put lights up, the electrical rules are the same as any other load — do not daisy-chain power strips, do not run cords under rugs or through doorways where they get pinched and damaged, keep outdoor connections GFCI-protected and dry, and if a circuit starts tripping, the answer is less load or another circuit, never a bigger breaker. This page is about safety and capacity only; when in doubt, text us a photo of the setup and ask.
What it costs (honestly)
Troubleshooting and service calls are $75/hr + $50 trip — that is the only rate we publish. Anything bigger is scoped to the 2020 NEC and quoted in writing from photos before work starts.
Text pictures of your panel (door open, labels visible) and the problem outlet or circuit to (412) 326-9761.
Common questions
Can I run a space heater on an extension cord or power strip?
No. A typical heater draws about 1,500 watts — roughly 12.5 amps sustained. Extension cords and power strips overheat under that draw. Wall outlet only, one heater per circuit, three feet from anything that can burn.
Why does my breaker trip more in winter?
Winter adds load to circuits that were fine in summer — heaters, heat tape, longer lighting hours. A breaker that trips repeatedly on the same circuit is a warning, not an annoyance. Have the circuit checked instead of resetting it all season, and never replace it with a larger breaker.
When should heat tape be checked?
Before the first freeze — this week, with lows of 32°F and 30°F forecast for Nov 16–17. It should be on a GFCI-protected outlet that has not tripped, with no damaged or overlapped cable.